1. Scope
This
specification covers single core armour for Medium Voltage cable
in
accordance with
SNI IEC 60502-2 : 2009 / IEC 60502-2 (3.6/6 kV ~ 18/30 kV)
SNI IEC 60502-2 : 2009 / IEC 60502-2 (3.6/6 kV ~ 18/30 kV)
Construction : Single core
A. Conductor : Plain Annealed Copper
B. Conductor screen : Semiconductive Compound
C. Insulation : Cross-Linked polyethylene
D. Insulation screen : Semiconductive Compound
E. Color Code : Natural
F. Metalic screen : Plain copper tape
G. Tapping : Suitable tape
H. Separation sheath : Polyvinyl Chloride color Black
I. Armour : Double Aluminium tape
J. Tapping : Suitable tape
K. Outer Sheath : Polyvinyl Chloride color Black or up to requested
3. Cable
shall be designed & tested in accordance with SNI IEC 60502-2 : 2009 / IEC 60502-2, IEC 60228
4. Special
Aplication / Performance up to request
- Available Product in accordance to SPLN, JIS, BS, ICEA/NEMA, AS Standard or other requirement.
-
Tin coated Copper conductor.
- Available Product in accordance to SPLN, JIS, BS, ICEA/NEMA, AS Standard or other requirement.
- Longitudinally water blocking characteristic
- Copper wire screen
- Polyethylene / Low Smoke Free Halogen sheath.
- Anti termite & Anti Rodent performance.
- Flame retardant test acc to IEC 60332-3 Cat. A, B or C.